Detailed Photos
Product Description
The air cooled water chiller 5hp industrial chiller water chiller machine cooling, also known as an air-cooled box-type industrial chiller unit, utilizes a air-cooled heat dissipation design. It draws surrounding air into the equipment using built-in fans and dissipates heat through a condenser, thereby reducing the system temperature. It does not require an additional water cooling system and is relatively easy to install and maintain.
NO |
Name |
Specification type |
Performance parameter |
1 |
unit |
Mould |
YSD-5HP |
2 |
Cooling capacity |
KW |
13.95 |
Kcal/h |
11990 |
3 |
power supply |
V |
5N-380-50HZ |
4 |
way to control |
type |
Capillary |
5 |
Total power |
A |
4.86 |
6
|
compressor |
Type |
Fully enclosed vortex type |
Cooling input power(kW) |
3.75 |
Type |
vortex type |
7
|
Fan |
Type |
External rotor axial flow fan |
power(KW) |
0.36 |
Air volume m3/h |
5000 |
8 |
Water pump |
Type |
Centrifugal clean water pump |
power(KW) |
0.37 |
Lift M |
18 |
flowL/MIN |
90 |
9 |
Condenser |
Type |
Aluminum fin sleeve copper tube type |
Cooling air volume(M3/h) |
5000 |
10 |
Evaporator |
Type |
coiled tube type |
Water volume m3/h |
2.4 |
Water solubility m3 |
0.065 |
11 |
Water tank |
Material |
SUS304 |
Volume L |
45 |
12 |
Piping |
Chilled water media outlet |
DN20(According to customer requirements) |
Chilled water media entrance |
DN20(According to customer requirements) |
Drain |
DN15(According to customer requirements) |
Tap water inlet |
DN15(According to customer requirements) |
13 |
Microcomputer controller |
Display status |
Key display |
Contribute |
305000A |
Power output selection |
Relay output |
Temperature control rangeºC |
+5~+35 |
Temperature control accuracyºC |
±2.0 |
14
|
Alarm device |
Abnormal temperature |
Circulating water temperature is too low alarm and cut off the compressor |
Power supply reverse phase |
Power phase detection prevents the pump and compressor from reversing |
High and low voltage fault |
The pressure switch detects the pressure status of the refrigerant system |
Compressor overload |
Thermal relay protects the compressor |
Compressor overheating |
Internal protector protects the compressor |
Pump overload |
Thermal relay protects the pump |
Low water alarm |
Water level switch |
Short circuit |
air switch |
Cold media |
Tap water |
15 |
Dimensions |
L*W*H(MM) |
1250*640*1250 |
16 |
Total Weight |
KG |
170 |
Application
Our team
FAQ
FAQ
1. Can you guarantee your quality if we order on you ?
Of course.Best quality is our principle all the time.You can be assured on our production.
2.What should I do if we are not able to operatethe the machine when we receive it?
Operation manual guides you the installation.Besides, we haveprofessional after-sale groupto customer 's site to solve any problems.weprovide 7*24 hours on-line technical support.
3.How could I get the spares on machines?
We will send extra sets of easy broken spares andaccessories likeo ring etc.Non-artificial damagedspares will be sent freelyduring 1 year 's warranty.
4.How to maintain such a machine ?
Please clean every part after filling thus can givelong using life of machine and make a carefullyclean 3 times a year.